A fire occurred on a flange of a hydro-desulphurisation unit during start-up operations. A failure of this flange caused of the leak.
A fire occurred on a valve of a hydro-desulphurisation unit in a refinery. The failed gland was modified and fire extinguishers by steams were installed permanently .
The fire started in a electrolysis cell. The fire originated from a hydrogen leak in the hydrogen over pressure control system of the cell and an unidentified ignition source. The ARIA report (sew…
A hydrogen leak occurred at the connection between a temperature measuring sleeve and a flange on the cleaning tower of a fertilizers plant (approximately 70% hydrogen, 21% nitrogen and the rest…
The incident occurred in the fired heater of a hydrocracking unit. Due to overheating, about 250,000 pounds of hydrogen and naphtha mixture were accidentally released into the firebox of the fired…
This incident occurred at the fired heater of a non-further specified reactor of a refinery (probably a hydro-desulphurisation unit). A tube of the fired box failed releasing a mixture of hydrogen…
A fire developed at the top of the flare stack of a during a violent thunderstorm, in a chemical plant (Seveso-classified). The flare stack is used to discharge hydrogen produced by the restarting of…
The incident occurred at the hydrogen coolant circuit, when purging the hydrogen with carbon dioxide and air, aiming at finding a leak. Following a preliminary investigation, the power plant company…
There was a massive explosion at one of the generator-turbine units of a coal-based power station. Undetected hydrogen leak from the generator was identified as a major trigger. According to the news…
The incident occurred at a power generator during the shutdown of one reactor unit. Hydrogen leaked from the cooling circuit of the generator due to damaged sealing. The hydrogen ignited. The fire…
Leaking hydrogen gas ignited causing a fire at a power plant.
A hydrogen leak sparked a fire at a power plant, burning a 30-foot hole in the roof. Only one of the plants four turbines were shut down.
A hydrogen leak occurred in in the cooling system of electricity generation part of the in a nuclear power plant. .
It was a small incident in a heat-electric power plant. The alarm was registered at 11:26 and the fire was extinguished at 12:03. The incident took place during tests using the reserve power…
One turbine was stopped for minor repairs and adjustment. The generator’s excitation breaker and air-operated disconnect breakers were opened. When the turbine generator had nearly completed its…
A hydrogen leak occurred on the a coolant pipe of an electrical generator located in the turbine building, at 200 m from the reactor. Because of the welding works ongoing at that moment on the pipe,…
A malfunction in the turbine-generator unit resulted in a fire and forced the operators to manually shut down the nuclear reactor. The seals containing the hydrogen hydrogen used as a coolant were…
The explosion occurred at a hydrogen drier used for the treatment of the hydrogen used as coolant in a power generator. The hydrogen leaked, entered the contactor panel box of the drier and was…
This incident occurred in the turbine compressor system. A severe hydrogen ingress into the stator coolant system resulted in a fire in the stator coolant head tank (ignition source unknown). No…
A leak of a compression fitting lead to the build up of an explosive air/hydrogen mixture in the generator pit. The ignition of the mixture was caused by corona discharge. The resultant explosion…
The compressor-turbine unit tripped while on on-load, due to a serious fire between alternator and one of the bearing. The failure of a generator slip ring and of the hydrogen seal caused the leak of…
The explosion occurred in the condenser area of a steam turbine, two hours after the unit tripped due to a stator earth fault. The stator earth fault had damaged two hydrogen cooler tubes, which…
Ejection of rotor wedge material lead to vibration induced failure of components, including hydrogen seals. Serious fire resulted from hydrogen leakage, which subsequently lead to an oil fire.…
Explosion of hydrogen at slip ring end of an alternator. It was caused by a hose fracture within the generator casing, which led to a discharge of water into the casing and subsequent electrical…
The incident started with the cracking of the low-pressure turbine blades. This caused an unbalance to turbine generator rotor which led to the failure of the bearings and the loss of confinement…
During a turbine testing at 100 percent power, a problem developed in the auto-stop trip system, which led to a turbine and reactor trip. The turbine stop valves closed as expected, but after closure…
SYNOPTICs The loss of the hydrogen side sealing oil pump and other problems in the sealing oil system resulted in the coolant hydrogen leaking from the generator. The hydrogen leaked for several…
A nuclear Power Plant experienced a main generator hydrogen fire. Although a senior reactor operator (SRO) and auxiliary operators from another shift were available immediately, the need to provide…
This incident occurred during maintenance works after an outage at a turbine and generator unit of the plant. At the time of the incident, 15 maintenance technicians had already been working on the…
A technical failure in the High-Pressure turbine blades caused high vibrations in lubricating oil pipes. Some pipes broke off and the oil leak caught fire from hot surfaces. Also the generator's…