Skip to main content

Fire at a fertiliser plant (67)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire at a fertiliser plant

A hydrogen leak occurred at the connection between a temperature measuring sleeve and a flange on the cleaning tower of a fertilizers plant (approximately 70% hydrogen, 21% nitrogen and the rest carbon monoxide and other impurities). Workers reported to the factory leaders, who issued the order to block the leak. Workers tried to use iron cards and rubber sheets to plug the leak, but failed. They were sent again to block the leak with tire. While doing so, the leaking hydrogen ignited, probably due to static sparks produced by the friction of the hydrogen flow against the tire rubber. The fire caused two fatalities. The accident caused direct economic losses of more than 340,000 yuan.

Event Date
March 13, 1993
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was a leak. The cause of the leak is unknown. The INGITION CAUSE was triggered by the attempt to stop the leak. The ROOT CAUSE was ill management: (i) the plant operator violated rules and regulations, issuing orders which disregarded basic health and safety principles; (ii) the worker were not provided with effective personal protection; (iii) there was a complete lack of emergency procedures, probably hinting at a lack of risk assessment.

Facility Information
Application Type
Application
Fertilisers production
Specific Application Supply Chain Stage
Components Involved

flange, cleaning tower

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
2
Property Loss (onsite)

340000

Post-event Summary

The fire caused two fatalities. The accident caused direct economic losses of more than 340,000 yuan.

Lessons Learned

The plant did not have in place effective emergency plan and probably was lacking as well of preventive and mitigating measures, such as the capacity to isolate that part of the facility where the leak occurred, to depressurise and purge it before starting any type of repair work. Even the materials provided to the workers to stop the leak was not respecting the minimal safety considerations for this type of emergency: rubber is an electrically isolator; its handling can easily generate electrostatic sparks able to ignite hydrogen. The incident reveals a complete absence or neglection of a proper risk assessment of operations.

Event Nature
Emergency Action

The workers were sent to stop the leak with completely wrong means and equipment, which eventually caused the leak to ignite

Release Type
Release Substance
H2 70% , N2 21%, CO 9%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Baibai safety net news of 2018-03-02: https://www. bbaqw. com/al/3022. htm (accessed September 2024)

B. Wang et al. , Hydrogen related accidents and lesson learned from events reported in the in east continental Asia,#2023, ICHS-2023