Fire at a generator of a power plant
The incident occurred at the hydrogen coolant circuit, when purging the hydrogen with carbon dioxide and air, aiming at finding a leak. Following a preliminary investigation, the power plant company explained that hydrogen was still present when air was injected, creating the condition for the formation of an explosive mixture.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause of he explosion seems to be the erroneous injection of air into the hydrogen lines. Acording to the sources, it appears also that this occurred by deviating from the prescribed procedure. If confirmed, the root cause could be related to a human error or errors during the communication of the instructions