Fire at a generator of a power plant
The incident occurred at a power generator during the shutdown of one reactor unit. Hydrogen leaked from the cooling circuit of the generator due to damaged sealing. The hydrogen ignited. The fire was extinguished after 1 hour 40 minutes.
Event Date
November 12, 2018
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause of the accident was the release of hydrogen from a sealing on the generator. The root cause is related to an electrical fault that caused the generator speed to suddenly rise from a still state to 1145 r/min, causing violent vibration of the generator rotor which lead to wear of the sealing leakage of hydrogen gas and the consequent hydrogen explosion. The cause of the ignition is probably an electrostatic spark.