Fire at a generator of a power plant (1019)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire at a generator of a power plant

There was a massive explosion at one of the generator-turbine units of a coal-based power station. Undetected hydrogen leak from the generator was identified as a major trigger. According to the news, some workers, unaware of the leak, were trying to fix some dirt blocks and loose nuts and bearings in the generator. Just below was an oil tank. Fire sparked spread in minutes up to 16 metres, setting off the blast “with a heavy noise”. It took hours to control the fire. Four persons were injured.
Event Date
November 13, 2019
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITATING CAUSE of the leak is unknown. The released hydrogen ignited possibly because of the activities of workers using non spark-free tools. Escalation may have occurred due to the proximity of an oil tank. There are also doubts on the proper or effective actions of the fire extinguisher. The ROOT CAUSE could be attributed in general to lack of safety measures, procedures and/or practices. Why were the workers not equipped with detectors?
Facility Information
Application Type
Application
coal-fired power plant
Specific Application Supply Chain Stage
Components Involved
turbine, Colling system
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE FACILITY The turbine-generator affected was a 500 megawatt and was commissioned in 2011. Hydrogen was used as coolant.
Operational Condition
Pre-event Summary
According to the news, some workers, unaware of the leak, were trying to fix some dirt blocks and loose nuts and bearings in the generator.
Consequences
Number of Injured Persons
4
Number of Fatalities
0
Lessons Learned
Undetected releases of hydrogen used as cooling agent of a turbine or generator are often the cause or contributor to sever damage of the unit (se for example HIAD event 1000). A procedure of the plant affected by this incident foresaw a shut-down in case of hydrogen leakage, but the plant was not shut-down. In this particular case it is unclear if the hydrogen leak had been checked and detected. Anyhow, the unit was not shut down before escalation took place.
Event Nature
Emergency Action
It took hours to control the fire. Probably also the fire extinguishers did not function effectively.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

DownToEarth. co news of 14/11/2019 https://www. downtoearth. org. in/news/energy/blast-in-anpara-d-power-station-67746 (accessed December 2019)