Fire at a generator of a power plant (271)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire at a generator of a power plant

A malfunction in the turbine-generator unit resulted in a fire and forced the operators to manually shut down the nuclear reactor. The seals containing the hydrogen hydrogen used as a coolant were likely damaged by abnormal turbine vibrations. The damage to the turbines and generator from the fire was minimal, but vibrations did damage the low pressure turbines, bearing supports and some steam piping.
Event Date
September 20, 2008
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The loss of containment of the hydrogen coolant was caused by the vibrations in the turbine, due to an imbalance from the loss of turbine rotor blades.
Facility Information
Application Type
Application
Nuclear power plant
Specific Application Supply Chain Stage
Components Involved
Turbine generator, generator coolant, hydrogen seals
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE FACILITY The fire occurred in the turbine hall on a 2,106 MW power pant. There were two units at the station: 1,029 MW and 1,077 MW . Unit 2 continued to operate at full power. The turbine generator transforms steam into electricity. Hydrogen is used to keep the generator cool during operation and the hydrogen is contain in seals.
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

The damage to the turbines and generator from the fire was minimal, but vibrations did damage the low pressure turbines, bearing supports and some steam piping. The NRC said all nuclear safety systems functioned as expected and were not affected by the fire, which occurred in a building separate from the nuclear reactor.

Investigation Comments

The NRC said all nuclear safety systems functioned as expected and were not affected by the fire, which occurred in a building separate from the nuclear reactor.

Event Nature
Emergency Action
The fire was extinguished 25 minutes after it started. . The operators manually shut the reactor. After the fire was extinguished, operators received a signal indicating a problem with the fire suppression system due to a rupture in the pipe that is a source of water for the plant's fire protection systems, the NRC said. Alternate sources of water were available for fire suppression in case they were needed.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Investigation of the US Nuclear Regulatory Commission

Reuter news of 20 September 2008

Also in H2TOOLS https://h2tools. org/lessons/hydrogen-leak-and-fire-nuclear-power-plant (accessed dec 2024)