Fire at a generator of a power plant
One turbine was stopped for minor repairs and adjustment. The generator’s excitation breaker and air-operated disconnect breakers were opened. When the turbine generator had nearly completed its shut down, one of the disconnect breakers closed spuriously and reconnected the generator to the grid again. The turbine generator accelerated to rated speed within 25 - 30 seconds. As a result, the generator rotor got into unbalance and its bearings were destroyed. Cooling hydrogen, sealing oil and lubricating oil caught fire. All feed water and emergency feed water pumps were lost. An alternative make-up water supply and reduction of primary circuit pressure prevented serious consequences.

INITIATING CAUSES The failure of the turbine was caused by its unplanned, accidental restart, due to the malfunctioning of a circuit breaker. ROOT CAUSE(S) Although the source does not report the root causes, from the extension of the fire and its consequence for the overall plant it can be plausibly assumed the same root causes as in the event HIAD ID = 042. The fire could spread up and cause such damage due to lack of measures against fire propagation and escalation.