Fire at a generator of a power plant
The explosion occurred in the condenser area of a steam turbine, two hours after the unit tripped due to a stator earth fault. The stator earth fault had damaged two hydrogen cooler tubes, which allowed hydrogen to pass from the stator casing into the condenser via the condensate system. The ignition source was thought to be either via a contact with the hot metal of the steam chests or due to an electrostatic spark.
Event Date
February 26, 1980
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences