Skip to main content

Fire at a generator of a power plant (278)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire at a generator of a power plant

The explosion occurred in the condenser area of a steam turbine, two hours after the unit tripped due to a stator earth fault. The stator earth fault had damaged two hydrogen cooler tubes, which allowed hydrogen to pass from the stator casing into the condenser via the condensate system. The ignition source was thought to be either via a contact with the hot metal of the steam chests or due to an electrostatic spark.
Event Date
February 26, 1980
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING cause the leak of damaged hydrogen pipes. Nothing can be said on the root cause, but the fact that the stator earth fault was able to damage the hydrogen pipe may be attributed to a design failure and/or shortcoming in the risk assessment.

Facility Information
Application Type
Application
unspecified type of power plant
Specific Application Supply Chain Stage
Components Involved
hydrogen pipe
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF A "STEAM CHEST" The steam chest serves as a distribution point for the high-pressure steam coming from the boiler.
Operational Condition
Pre-event Summary

A stator earth fault had occurred two hors before the incident and damaged the hydrogen coolant system.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description provided by HSE, original source confidential