Fire at a generator of a power plant (272)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire at a generator of a power plant

The explosion occurred at a hydrogen drier used for the treatment of the hydrogen used as coolant in a power generator. The hydrogen leaked, entered the contactor panel box of the drier and was ignited by a spark from the solenoid valve. The leak was caused by the corrosion of a hydrogen dryer cylinder. Explosion blew off contactor panel door. No injuries sustained and no other area of plant was damaged.

Event Date
December 9, 1972
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

INITIATING CAUSE: The leak was caused by the corrosion of a hydrogen dryer cylinder. Explosion blew off contactor panel door. ROOT CAUSE: In absence of details, it could have been one of the following: lack of proper maintenance/inspection design shortcoming Management decision to operate the system beyond the max allowed age

Facility Information
Application Type
Application
unspecified type of power plant
Specific Application Supply Chain Stage
Components Involved

hydrogen dryer

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Emergency Action

Not known

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Event description provided by HSE, original source confidential