Fire at a generator of a power plant
The explosion occurred at a hydrogen drier used for the treatment of the hydrogen used as coolant in a power generator. The hydrogen leaked, entered the contactor panel box of the drier and was ignited by a spark from the solenoid valve. The leak was caused by the corrosion of a hydrogen dryer cylinder. Explosion blew off contactor panel door. No injuries sustained and no other area of plant was damaged.
Event Date
December 9, 1972
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

INITIATING CAUSE: The leak was caused by the corrosion of a hydrogen dryer cylinder. Explosion blew off contactor panel door. ROOT CAUSE: In absence of details, it could have been one of the following: lack of proper maintenance/inspection design shortcoming Management decision to operate the system beyond the max allowed age