Fire at a generator of a power plant
The compressor-turbine unit tripped while on on-load, due to a serious fire between alternator and one of the bearing. The failure of a generator slip ring and of the hydrogen seal caused the leak of hydrogen. The hydrogen ignited perhaps caused by contact with hot surface), resulting in a combination of hydrogen and oil fires. The fire extinguished by fire brigade. No injuries. Serious site damage was sustained to in CT chamber and alternator end of generator.
Event Date
October 13, 1979
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING cause was the hydrogen seal and of the generator slip ring. The source identified the failure of the seal as "caused by circulating current", what unfortunately is not clear. Nothing can be said on the root cause