Skip to main content

Fire at a generator of a power plant (277)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire at a generator of a power plant

The compressor-turbine unit tripped while on on-load, due to a serious fire between alternator and one of the bearing. The failure of a generator slip ring and of the hydrogen seal caused the leak of hydrogen. The hydrogen ignited perhaps caused by contact with hot surface), resulting in a combination of hydrogen and oil fires. The fire extinguished by fire brigade. No injuries. Serious site damage was sustained to in CT chamber and alternator end of generator.
Event Date
October 13, 1979
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING cause was the hydrogen seal and of the generator slip ring. The source identified the failure of the seal as "caused by circulating current", what unfortunately is not clear. Nothing can be said on the root cause

Facility Information
Application Type
Application
unspecified type of power plant
Specific Application Supply Chain Stage
Components Involved
hydrogen seal
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Emergency Action
Fire extinguished by fire brigade.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description provided by HSE, original source confidential