Fire at a generator of a power plant
This incident occurred during maintenance works after an outage at a turbine and generator unit of the plant. At the time of the incident, 15 maintenance technicians had already been working on the unit since more than 10 days. An access cover was removed causing the release of hydrogen and resulting in multiple explosions and fires. The explosion was heard 35 miles away. The blast tore a huge section from a building holding the six coal-fired generators of the plant and caused three fatalities and several injuries. The hydrogen was used as cooler of the unit. The hydrogen system should have been depressurised and purged before its opening, because the workers assumed that these operations had already been done before (they are usually performed in the 2-3 first days of a maintenance intervention).
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE was the accidental release and ignition of hydrogen used for the cooling of the turbine and generator unit. The release was due to the failing of following the safe procedure, what brings to the following ROOT CAUSES: (i) lack of or shortcoming in supervision of the maintenance work, which could reveal Inadequate process safety management, (ii) lack of or shortcoming in communication between maintenance contractors and plant personnel, (iii) lack of or shortcoming in regulatory oversight (according to the ICHEME source, there have been no plant audit despite several leaks, fires and explosions since 1992).