Fire at a generator of a power plant
During a turbine testing at 100 percent power, a problem developed in the auto-stop trip system, which led to a turbine and reactor trip. The turbine stop valves closed as expected, but after closure they re-opened due to the fact that some solenoid-operated valves of the turbine protection system failed to open. Steam flow to the turbine led to an over-speed of about 160 percent of rated speed. The low-pressure turbine blades broke and penetrated the turbine shroud. A hydrogen explosion and fires and turbine lubricating oil fires resulted. The damage in turbine generator systems was extensive, for instance the turbine, the generator and the main condenser were damaged.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING CAUSES The failure of the turbine was caused by its accidental re-start despite the fact that a reactor shut down was ongoing. ROOT CAUSE The fact that a series of malfunctioning led to the restart of the turbine indicates the safety systems were not properly designed, or at least not well integrated in an overall risk assessment considering also the emergency procedures.
