Skip to main content

Fire at a electrolyser in a chemical plant (920)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire at a electrolyser in a chemical plant

The fire started in a electrolysis cell. The fire originated from a hydrogen leak in the hydrogen over pressure control system of the cell and an unidentified ignition source. The ARIA report (sew references) calls this control system a "hydrogen guard". The hydrogen leak comes from a lack of water in the guard due to the lack of filling of the guards by the operators and their flushing. The flushing of the hydrogen through the guard was caused by the rise in pressure of the hydrogen line due to the activation of the chlorine burner. This one had detected a drop in hydrogen pressure probably due to pressure losses due to frost-related blockages. In addition, operators had not performed the filling of the water sear in the hydrogen guard because of to the imminent shutdown of electrolysis. They were also busy managing smokes on several cells. There were no clear instructions to prioritize level verification in the hydrogen water sear.
Event Date
January 14, 2017
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Facility Information
Application Type
Application
Chlorine production
Specific Application Supply Chain Stage
Components Involved
electrolyer, hydrogen guards
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Lessons Learned
The ARIA report does not directly lesson learnt elements. Nevertheless, it should be investigated if it is possible to provide efficient passive barriers in case of active barriers deactivation. Also procedures (control) and their priority should be reviewed.
Event Nature
Emergency Action
No information in the ARIA report, except that the emergency stop was triggered and the fire was extinguished with the help of fire extinguishers and wet mop to cool the cell cap.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/49539/ (accessed September 2020)