HIAD Event Initiating System: Hydrogen System Initiating Event


Pressure buildup in tank was manually vented by driver releasing 1000 cu ft [Zalosh and Short, 1978]

The tank of a liquid hydrogen tanker was manually vented prematurely on its empty return trip. 9,000 cu ft werereleased [Zalosh and Short, 1978]

While returning to the base, a liquid hydrogen tanker had to be vented twice. The cause of the overpressure was a malfunctioning scale which allowed a slight overload of hydrogen. [Zalosh and…

At a hydrogen production facility, the hydrogen compressor used to store hydrogen at approximately 20 MPa failed due to the rupture of the casing (spacer) connecting the hydraulic drive unit and…

A hydrogen leak occurred at a plant's hydrogen fill station. After having transferred the load to the plant station storage system, a tube trailer pulled away and caught a hydrogen fill line.…

This near-miss occurred at a company producing compressed gas bottles according to customers requests. When preparing a gas mixture containing oxygen and nitrogen, by mistake hydrogen was added,…

At an off-site LH2 fill station, a LH2 trailer hit the GH2 purge shut-off valve handle. The tubing attached to the purge valve was bent on both ends but did not leak. [Ordin, NASA (1974)]

During a welding operation on a LH2 fill line it was discovered that LH2 was still in the tank although it should have been drained. Hence the potential for a major explosion existed. [Ordin, NASA…

An operator noted a loose tube sheet flange stud on a high temperature, high pressure heat exchanger in an hydrodealkylation unit. The stud was found to be cracked through. Analysis proved to be made…
A chemical mobile intervention unit intervened in the faculty to neutralize in an envelope sealed an experimental device likely to release hydrogen. The faculty was evacuated during the intervention.

A fuel cell and hydrogen vehicle terminated the refueling, but the dispenser nozzle could not be completely disconnected from the the vehicle receptacle. It could be disconnected only after…

An LH2 trailer-tractor was returning to the base after a hydrogen delivery at a customer. The trailer was almost empty. Nevertheless, the drivers noticed an increase in the trailer internal…

An LH2 trailer-tractor was returning to the base after a hydrogen delivery at a customer. The trailer was almost empty. Nevertheless, the drivers noticed an increase in the trailer internal…

An LH2 trailer had just delivered hydrogen to a customer. The vehicle exited the plant, weighted the trailer parked to get the weight receipt. While in the building, a safety device activated due…

A LH2 trailer had delivered hydrogen to a customer and on the way was heading back to base, when the tank pressure rose from 40 psi to 128 psi. The drivers stopped at a truck parking place and…

A LH2 trailer was traveling to delivery hydrogen to a customer, while the drivers noticed an increase in trailer pressure. To avoid the possibility of having the safety vent open while on the road…

A LH2 trailer/truck had delivered liquid hydrogen to a customer site and was travelling back empty to the base. The drivers noticed an increase in trailer pressure. To avoid the possibility of…

A LH2 trailer had just delivered hydrogen to a customer and was travelling on a highway returning to the base, when the driver noticed that the pressure inside the tank was increasing rapidly. The…

The incident occurred during a temporary shutdown of the distillate hydro-treatment unit. The crude oil distillation units main column overhead product was pumped to a gasoline storage tank via the…

A full liquid hydrogen tanker was travelling from the home terminal to deliver to a customer, when the drivers noticed a pressure rise during a safety check. The drivers called in and were…