Over-pressure damage to a storage tank in a refinery
The incident occurred during a temporary shutdown of the distillate hydro-treatment unit. The crude oil distillation units main column overhead product was pumped to a gasoline storage tank via the straight run gasoline rundown line. When restarting the distillate hydro-treatment unit, a valve in the start-up line to the high pressure separator branching off the crude oil distillation unit main column overhead product line was opened before the line to tank was closed. Hydrogen gas at a pressure of 30 bars consequently reached the tank, caused an overpressure and caused substantial damage. The tank shell was lifted upwards by approximately 110mm. No one was injured in the incident and there was no leakage of liquid product.
Event Date
July 11, 1989
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was an operation error, a wrong sequence of opening and closing of the valve connecting the storage tank to the high pressure section of the hydrocracker, with consequence entrance of hydrogen at 30 bars to the tank. The ICHEME report (see reference) does not mention the root CAUSE, but the operation error seems to hints at inadequate operative instruction and risk assessment.