Mix-up of hydrogen and oxygen in a gas production plant
This near-miss occurred at a company producing compressed gas bottles according to customers requests. When preparing a gas mixture containing oxygen and nitrogen, by mistake hydrogen was added, instead of nitrogen. The pipelines did not have clear labelling. The mistake was discovered during analysis, when a small gas sample (less than 5 ml) ignited during flashing.
Event Date
November 24, 2003
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was a human error in connecting the wrong pipeline. A contributing CAUSE was the lack of clear labelling of the pipelines gases. The root CAUSE could be attributed to management, which did not consider the risk of gas mixing up and did not adopted preventing measures such as different connector for different (incompatible) gases.