Mishap at a HRS caused by a CGH2 tube trailer (911)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Mishap at a HRS caused by a CGH2 tube trailer

A hydrogen leak occurred at a plant's hydrogen fill station. After having transferred the load to the plant station storage system, a tube trailer pulled away and caught a hydrogen fill line. The driver of the trailer did not properly stow the line after filling and failed to verify that it was clear of the trailer before leaving. The hydrogen fill line caught on the trailer and subsequently pulled on the distribution manifold which was regulating the distribution of the refuelling station stationary storage tubes. The force exercised by this pull bent the manifold and hydrogen began leaking from a threaded connection and from the hydrogen fill line. The escaping hydrogen did not ignited. The fire department and the service technician of the hydrogen delivery company stopped the leak at the stationary ground tube storage system by closing the individual valves on each hydrogen storage tube. H2TOOLS report

Event Date
August 25, 2008
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the damage to the pressure control manifold under the force of the flexible line pulled away by the trailer. The ROOT CAUSE was mainly a negligence of the trailer driver. In absence of a connection breakaway, the accidental scenario of the trailer leaving with the fill line still attached should be given more attention.

Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved

filling line, manifold

Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary

The filling operation had terminated and the trailer was ready to drive away.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (offsite)

0

Post-event Summary

The manifold and the filling line were damaged. The damaged hydrogen stationary storage unit was replaced it with a hydrogen tube trailer with concrete barriers installed to provide protection.

Lessons Learned

(i) Trailer drivers need to be trained on delivery procedures and emphasize made aware of the consequence of mishaps related to connections and disconnections. (ii) The procedures for hydrogen delivery, including the preparatory and the end-of-operations steps, must be site-specific. (iii) Verification of the proper execution of the actions must be part of the procedure prior to departure, possibly by means of a checklist, to verify that the conditions enabling a safe trailer movement are in place.

Event Nature
Emergency Action

6:45 PM The truck trailer driver reported hearing a "pop and hissing sound", stopped the trailer-truck movement, and then promptly left the truck to report the incident. The local fire department was contacted and the building was evacuated. 8:00 PM The fire department arrived, together with the hydrogen delivery company service technician. The hydrogen leak at the plant's hydrogen ground storage system was stopped by closing the individual valves on each hydrogen storage tube. 10:00 PM, The all clear was given. Hydrogen operations were restored to the plant the next day

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Event description in the US database H2Tools/Lesson Learned https://h2tools. org/lessons/hydrogen-delivery-truck-causes-hydrogen-leak-fill-station-due-improperly-stored-hydrogen (accessed October 2024)