Mishap at a HRS caused by a CGH2 tube trailer
A hydrogen leak occurred at a plant's hydrogen fill station. After having transferred the load to the plant station storage system, a tube trailer pulled away and caught a hydrogen fill line. The driver of the trailer did not properly stow the line after filling and failed to verify that it was clear of the trailer before leaving. The hydrogen fill line caught on the trailer and subsequently pulled on the distribution manifold which was regulating the distribution of the refuelling station stationary storage tubes. The force exercised by this pull bent the manifold and hydrogen began leaking from a threaded connection and from the hydrogen fill line. The escaping hydrogen did not ignited. The fire department and the service technician of the hydrogen delivery company stopped the leak at the stationary ground tube storage system by closing the individual valves on each hydrogen storage tube. H2TOOLS report

The INITIATING CAUSE was the damage to the pressure control manifold under the force of the flexible line pulled away by the trailer. The ROOT CAUSE was mainly a negligence of the trailer driver. In absence of a connection breakaway, the accidental scenario of the trailer leaving with the fill line still attached should be given more attention.