Skip to main content

HIAD Nature Event - Release Type: Mixed


In a chlorine electrolysis facility, a mixture of oxygen and hydrogen in one of the electrolyser cells a short-circuit ignited causing a deflagration. The cover of the cell was a thin plastic film…
An explosion occurred at a chlorine production plant during the restart of the installation. An hydraulic syphon had probably been blocked by fire extinguishing products following a previous fire on…
An explosion at a coal plant occurred as a steam methane reformer was being reactivated.
In a residual-oil hydrotreatment unit (also called residual oil hydrogenation) plant, a hydrogenation unit caught fire with a huge bang, followed by a fireball in the form of a mushroom cloud. Black…
An explosion occurred in a hydrocracking reactor fitted with TOC which is a automatic cut-off system for raw oil and hydrogen supply. On the day of the incident, the operation was stopped with TOC…
The event occurred in the steam condensing line of the residual heat removal system the nuclear reactor. Radiolysis generated hydrogen and oxygen, which then accumulated in high concentration in the…
A gas mixture (25% nitrogen, 73% of hydrogen, 2% methane) leaked, due to the ejection of the check valve from its connection with the inlet pipe. A large amount of the gas mixed with air and ignited,…
This incident occurred when subcontractor two workers were widening air vents on the roof of a building hosting a tank containing hydrogen chloride solution. This intervention was necessary to to…
A fire and explosion occurred at a catalytic reformer unit. The fire centred between the reactors and fired heaters of the reformer and resulted in extensive damage to the unit. The explosion rocked…
The accident occurred in the hydro-cracking unit, specifically in its sulphur recuperating system. The location was on a 8" piping, which cracked at a a 90° bend. Due to the loss of confinment, a…
Ignition of hydrogen produced by washing slag in a tank for chlorosulfonic acid.
[Note of HIAD Validator: the presence of hydrogen and its role in the explosion is only one of the two possible explanations of this incident] The explosion occurred in a chemical reactor tank of a…
The incident affected a linear alkyl-benzene (LAB) plant. The plant was down for routine maintenance when an explosion occurred. An explosion and fire occurred at a 3000-gallon (approx. 11400 l)…
A lightning strike caused a voltage drop on the power supply of a chlorine-alkali plant using the mercury process. The emergency electrical system was activated, though restoring the external supply…
The incident occurred at the chlorine electrolyser. Failure of a strainer allowed sand from brine filters to get into mercury cells in a chlorine plant. It appears that the sand obstructed the flow…
During chlorine-alkali electrolysis an accident occurred in which chlorine was released due to a chlorine-hydrogen explosion. The person charged with the control of the measurements was informed by…

A hydrogen gas release occurred a fire last week at a chromium ore mine, forcing a temporary suspension of operations at the facility. Three workers were injured. Hydrogen emissions had already…

The explosion involving hydrogen gas knocked a 36-by-70-foot hole in the roof of the plant. Officials said the gas was formed when chemicals mixed in the plant's waste treatment unit.
The vent occurred in the ammonia production unit. A minor leak had been detected in a flange on the piping of the ammonia synthesis loop (operating at 250 bar). The company called a specialized…

This incident occurred at a fired heater of an ethylene unit of a chemical plant. The fired heaters was shutdown. A mixture of hydrocarbons and hydrogen flew back from the unit to a tube of the…