Explosion at a chlorine production plant
An explosion occurred at a chlorine production plant during the restart of the installation. An hydraulic syphon had probably been blocked by fire extinguishing products following a previous fire on the hydrogen exhaust system. While restarting the chlorine production unit, the hydrogen pressure started to increase, allowing hydrogen to permeate through the electrolyser membrane into the chlorine compartment. The chlorine /hydrogen mixture then entered the chlorine drying unit before exploding. The explosion was probably initiated by a discharge of static electricity or UV radiation. The internal emergency plan was started. The were not victim. The desiccation towers were destroyed and the chlorine manifold damaged. The increase in the chlorine’s hydrogen content had been detected by an on-line analyser 15 minutes prior to the explosion.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was the clogging of the hydrogen venting pipe. The root cause were ill-designed procedures: inappropriate hydrogen firefighting means or insufficient with regard to (i) inappropriate hydrogen firefighting means, (ii) detection of overpressure in the hydrogen manifold, (iii) detection of hydrogen in the chlorine compartment, (iv) operating procedures to reduce these values.