Explosion in a fertilisers plant

The vent occurred in the ammonia production unit. A minor leak had been detected in a flange on the piping of the ammonia synthesis loop (operating at 250 bar). The company called a specialized external contractor to perform an on-stream repair of the valve. This solution was chosen because of for the limited extents of the leakage and the economic costs and efforts associated to a shut-down of a very complex system. The on-stream repair consisted in: (1) fabrication of a special bracket in two parts adapted to the dimensions of the flange of the valve, and (2): injection of filling material in the bracket around the flange (the material had to be injected at a pressure higher than the operating pressure inside the pipe). During the repair some stud bolts broke causing the escape of a jet of a gaseous mixture of unknown amount of hydrogen and nitrogen at 250 bars. The escaping mixture exploded, killing 2 workers and damaging the valves and the piping.
Event Date
February 23, 1989
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause was the failure of a flange followed by the release of a nitrogen-hydrogen mixture. The investigation revealed that two causes have probably contributed to the accident:(1): the flange stud-bolts of the valve have been replaced by others made of a material not equivalent to the one originally specified;(2): the maintenance company performing the repair have not taken into account the overpressure on the stud-bolts due to the injection of the filling material in the bracket. Therefore the root cause could be identified in the lack of a proper risk assessment of the repairing operation.
Facility Information
Application Type
Application
Fertilisers production
Specific Application Supply Chain Stage
Components Involved
flange, bolt, ammonia synthesis loop, valve, bracket
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
Following the detection of a small leak repairing works had been subcontracted, to be performed while the plant continued its operation.
Consequences
Number of Injured Persons
0
Number of Fatalities
2
Event Nature
Emergency Action
After the explosion, the ammonia production unit was shut-down. No off-site emergency measures were necessary.
Release Type
Release Substance
H2 75% N2 25%
Hydrogen Release Concentration (%)
0.00
Release Pressure (bar)
250.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References