Explosion at a chlorine electrolyser
In a chlorine electrolysis facility, a mixture of oxygen and hydrogen in one of the electrolyser cells a short-circuit ignited causing a deflagration. The cover of the cell was a thin plastic film which broke as planned. The production was stopped. According to the investigation, the inlet line of the electrolyte in the cell was blocked, which lead to an increase of the temperature in the cell and to the increase of oxygen production. On top of that, the alarm related to temperature control did not function.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was a malfunction in the cell of a chlorine electrolyser. Contributing cause was the malfunctioning of the alarm system related to the temperature monitoring of the process. The root cause was probably an underestimation of this hazard in the safety design of the process. Nevertheless, a correct mitigating measure (weak enclosure to reduce the risk of a e deflagration) operated as designed and limited damage,