Explosion in a chlorine production plant
A lightning strike caused a voltage drop on the power supply of a chlorine-alkali plant using the mercury process. The emergency electrical system was activated, though restoring the external supply voltage in less than 200 ms rendered the entire system inconsistent; some units were operating normally, but all units connected to the emergency devices (including the mercury pump) remained idle. An explosive mix of 500 kg of chlorine and an unknown amount of hydrogen accumulated inside the low-pressure chlorine treatment circuit. When the mix exploded, it injured two employees and destroyed the whole circuit (damage: 237 000 euros).
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was the loss of power due to lightning. The power recovery system was not considering that several components would have not properly reacted to micro-losses.