Explosion at the cracking unit of a refinery
The accident occurred in the hydro-cracking unit, specifically in its sulphur recuperating system. The location was on a 8" piping, which cracked at a a 90° bend. Due to the loss of confinment, a mixture of flammable gases was released from the pipe, which ignited in contact with air and exploded. This was followed by a fire. The released gas was recycled process gas consisting of 80 vol% hydrogen, 14 vol% methane, 1. 8 vol% hydrogen-sulphide , rest C2, C3 and C4 gases and water vapour. A large part of the plant was destroyed. The fire was mainly sustained by the petroleum derived. The smoke cloud was not toxic.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was the release and ignition of process gas through a crack in a high-temperature pipe. Other bends in the same piping were not corroded. The pipe had been the object of regular inspection, when its wall thickness was regularly measured: it was found abnormal corrosion. An inadequate inspection can be excluded as root cause. The ROOT CAUSE could be identified in some design shortcoming. It is known that sharp bends in gas pipes operating under harsh pressure and temperature conditions are weak elements, because bending causes microstructural phenomena acting as stress intensifiers of the base pipe metals, and because bends causes additional stresses due to changes in gas flow direction.