Explosion in a fired heater of an ethylene plant
This incident occurred at a fired heater of an ethylene unit of a chemical plant. The fired heaters was shutdown. A mixture of hydrocarbons and hydrogen flew back from the unit to a tube of the fire heater, where it accumulated, ignited, and exploded, causing extensive damage to the fired heater. The plant had decided to shut down all fired heaters due to the extreme cold weather caused by a winter storm. This had already caused several freeze-related operational issues, such as utility losses and supplier-driven gas shortages. However, a valve between one of the fired heaters and the downstream equipment remained open. The open valve allowed downstream flammable hydrogen and hydrocarbon gas to flow backward into the fired heater tubes. Approximately 30 minutes one of the tube ruptured, allowing the flammable gas to enter the firebox. [Note of the HIAD validator: for events triggered by the same storm, see event #1168, occurred at a different plant, and #1056, which affected a pipeline providing hydrogen to the plants. ]

The INITIATING CAUSE was the failure of a valve to isolate the ethylene reactor, allowing flow back of a flammable mixture. The fired heater tube filed due to thermal stress due to the rapid shutdown. The IGNITION was probably caused by the hot insulation within the firebox likely ignited the flammable gas, resulting in an explosion. CONTRIBUTION and ROOT CAUSES were (i) The decision to shut-down the fired heater tubes without decoking. Coke fouling can insulate the tube surface, resulting in local hotspots and increasing the risk of thermal shock and tube failure in fired heaters. These conditions stressed the tube’s walls when the metal cooled faster than the internal coke, breaking the tube. (ii) Inadequate winterization of multiple valves, instruments, and control systems contributed to the incident.