Explosion in a chlorine production plant
During chlorine-alkali electrolysis an accident occurred in which chlorine was released due to a chlorine-hydrogen explosion. The person charged with the control of the measurements was informed by an acoustic signal that a short circuit had occurred in one of the cells. This occurrence is not exceptional and is generally caused by a slight pressure fluctuation in the hydrogen system, which is passed back through the sloping connection between the hydrogen and the chlorine sections. Searching the cause of the increased hydrogen pressure, the controller found out that the hydrogen compressor, which removed all hydrogen from the plant, had stopped. The controller tried to restart the compressor, which succeeded in the first instance. But short time afterwards, the aggregate shut down again, due probably to the low-pressure blocking system caused the break down of the aggregate. The crew observed at that time that a considerable release of hydrogen occurred from the small pipes of the amalgam decomposers. The reason of it was the insufficient purge of hydrogen over roof passing through a hydraulic guard foreseen for such cases. This hydraulic guard has the function to transport hydrogen without danger over the roof. On the day of the accident, however, the function of the safety devices was limited by a non-negligible dirt deposition had formed inside, which increased the counter pressure. This situation was not recognised. Hydrogen reached the cell-space through the mercury pump, which transfers the regenerated mercury again in the electrolytic cell. This fast and massive intrusion of hydrogen caused a local formation of an explosive mixture. The first heavy explosion destroyed a part of the cells as well as the chlorine collection pipe passing under the explosion point. The plant was shut down by emergency shut down by the crew immediately after the explosion, but the ongoing decomposition of the amalgam did not stopped the production of hydrogen. Following that, another heavy explosion occurred, which destroyed the externally passing chlorine collection pipe.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
According to the source, the electrolyser was working as expected, and there was no sign of any malfunctioning of the safety functions. Therefore the INITIATING/direct cause, which was a material malfunctioning, could be also the root cause. However, again according to the source of the incident, the malfunctioning of the hydraulic guard (which is a safety device) remained unnoticed because a significant amount of dirt had accumulated. This points at a lack of maintenance and/or at a shortcoming of the guidelines.