While returning to the base, a liquid hydrogen tanker had to be vented twice. The cause of the overpressure was a malfunctioning scale which allowed a slight overload of hydrogen. [Zalosh and…

A hydrogen leak occurred at a plant's hydrogen fill station. After having transferred the load to the plant station storage system, a tube trailer pulled away and caught a hydrogen fill line.…

This near-miss occurred at a company producing compressed gas bottles according to customers requests. When preparing a gas mixture containing oxygen and nitrogen, by mistake hydrogen was added,…

A potentially explosive situation was reported by safety inspectors at a nuclear waste tank. The waste slurry had formed a thick crust which was trapping hydrogen being continuously generated…

During a welding operation on a LH2 fill line it was discovered that LH2 was still in the tank although it should have been drained. Hence the potential for a major explosion existed. [Ordin, NASA…

An LH2 trailer-tractor was returning to the base after a hydrogen delivery at a customer. The trailer was almost empty. Nevertheless, the drivers noticed an increase in the trailer internal…

An LH2 trailer-tractor was returning to the base after a hydrogen delivery at a customer. The trailer was almost empty. Nevertheless, the drivers noticed an increase in the trailer internal…

A LH2 trailer had delivered hydrogen to a customer and on the way was heading back to base, when the tank pressure rose from 40 psi to 128 psi. The drivers stopped at a truck parking place and…

A LH2 trailer was traveling to delivery hydrogen to a customer, while the drivers noticed an increase in trailer pressure. To avoid the possibility of having the safety vent open while on the road…

The incident occurred during a temporary shutdown of the distillate hydro-treatment unit. The crude oil distillation units main column overhead product was pumped to a gasoline storage tank via the…

A full liquid hydrogen tanker was travelling from the home terminal to deliver to a customer, when the drivers noticed a pressure rise during a safety check. The drivers called in and were…

A liquid hydrogen tanker was travelling from the home terminal to delivery to a customer. After approximately 7 hours and 400 miles, the drivers noticed hydrogen venting from the vent stack. They…

An empty tanker was returning to the home terminal after delivery to a customer. However, the drivers had failed to properly stabilize the residue pressure in the tank before departing from the…
A full liquid hydrogen tanker was approaching a stop at a vehicle weight station, when the driver noticed vapours coming from the tank vent. The driver parked the vehicle, inspected the tanker and…

The second stage of the Saturn V (S-II-T) was under full-duration static test, when one fire near LH2 valves of the LH2 tank and another in the engine area caused the automatic termination of the…

A liquid hydrogen tanker had been slightly overloaded. This forced the drivers to performed a manually venting releasing 5000 cu. ft. of hydrogen. [Zalosh and Short, 1978]

During a leak check of a flash point material testing chamber, the chamber was inadvertently over-pressurised with GH2. The glass port in the door burst, causing damage to the chamber and to the…

While a H2 sample was being prepared for an analysis, one of two cryogenic sample bottle disks ruptured and the gas ignited. [Ordin, NASA (1974)]

A CGH2 tube trailer was transferring hydrogen to a customer cylinder skid. The pressure relief on the customer system opened, the escaping hydrogen ignited and burned for approximately 10-15…

The vessel affected by the incident was a gas storage used for the hydro-desulphurisation process. The desulphurisation gas had high hydrogen content. The vessels had cracks in the upper transverse…