An explosion occurs in the oxygen gas holder in an electrolysis plant. The explosion was due to the entry of hydrogen in the oxygen gas holder. The dome of the gas holder and the collar were blown…

The incident occurred at the hydrofining unit, refining a mixture of petroleum and diesel into Euro 3 and Euro 4 diesel. A pump feeding the reactor with the process mixture failed. Following the…

An explosion occurred in hydrogen compressor, followed by a fire, due to rupture of 4 inch suction pipe to the compressor. "there was a substantial release of hydrogen, which exploded and continued…

A hydrogen-air explosion occurred outside a hydrogen compressor. Gaseous hydrogen was released from the vent stack due to a premature activation of a relief valve. The flammable atmosphere ignited…

A hydrogen compressor had been shut down for repairs and was being put back into service when the explosion occurred, causing damage . The compressor was equipped with interchangeable in­ take and…

The incident involved an hydrogen-on-demand unit (HOD), which was installed inside an environmental test chamber used for reliability tests. An employee was troubleshooting the chamber, assessing the…
A crack occurred in a storage tank (300 kg of hydrogen) releasing gaseous hydrogen to atmosphere. The vapour cloud exploded with an apparent centre of explosion 9 m above ground, with a energy…
In an electricity production plant, hydrogen leaked from a tank supplying the colant to the generator. The leaked hydrogen iognited and formed a fireball. Possible involvement of sealing oil not…

An explosion of hydrogen gas occurred on a test bench at a factory manufacturing rocket engins. The effect was perceived several kilometres away. The explosion was caused by the release of 8 kg of…

A special test was being executed to evaluate a high-pressure fuel turbo-pump lift-off seal. During the test, an open-air explosion took place on the test stand. There were no injuries, but non…

An explosion, accompanied by abundant black smoke, occurred at an ammonia production plant. An ignited leak of hydrogen in the ammonia production unit had spread to the pressure circuit carrying…
The explosion followed a hydrogen leak on a unit conditioning hydrogen. The leak was caused by the mechanical rupture of the membrane of a pressure release device which was part of a pressure…

[Note HIAD validator: this an incident where the hydrogen systems were invovled as effects of the initiating event. There is nevertheless and addtional possible contribution by hydrogen…

An explosion occurred during calibration of engine. The equipment was covered by a shed and when the valve was operated allowing hydrogen gas to flow through the engine, the gas ignited. The…

A process operator was working on a hydrogen tank in a mechanical workshop. The goal of the onoging operation was the removal of the collar from a hydrogen cylinder. An electric crosscut saw was used…

A series of explosions occurred in thee desulphurisation and catalytic reforming unit of the refinery, followed by fires in the same unit. The establishment is classified as Seveso Upper Tier…

A common vent system was used to connect vent lines from liquid hydrogen storage vessels to the vent stack (which was lit flaring the gas). Low order detonations were observed around the vent…

The incident occurred when filling a gaseous tube trailer from a liquid hydrogen stationary storage system. The liquid hydrogen cryogenic pump shaft malfunctioning caused a series of explosions…

Workers were connecting a compressed hydrogen cylinder, when a release of hydrogen occurred within a safety-box for flammable gases (a safety cabinet). During the emergency response procedures, the…

During the J-2 engine testing program, the engine start tank was pressurised. The pressure raised to an excess of 1500 psi (ca. 105 bar). The venting of the tank was attempted but remained…