Explosion on an ammonia reactor of a fertilizers plant.
An explosion, accompanied by abundant black smoke, occurred at an ammonia production plant. An ignited leak of hydrogen in the ammonia production unit had spread to the pressure circuit carrying synthesis gas(mixture of nitrogen N2, H2 and NH3 already synthesized), damaging the hydrogen compressor . 7 operators on site at that moment operated the emergency stop and evacuated the unit to the fall-back zone (reinforced control room), due the risk of a toxic leak. The plant operator triggered the emergency plan around 20 minutes later, alerted the public rescue service and the crisis team of the prefecture. Firefighters took over from the in-house firefighters who were watering the accident unit with three water spears to prevent the spread of the fire. In the control room, the production team flushed the synthesis gas circuit with nitrogen to remove the hydrogen and stopped the machines in the workshop while a lower secondary explosion occurred. The operator closed the water networks of the site to avoid pollution of the river Seine by the extinction water. For lack of fuel, the fire went down gradually around one hour after its start. Toxicity measurements (NH3) were performed in the unit and around the site by fixed and mobile sensors. While downwind around the site the measurements did not reveal any dangerous concentration; 200 ppm was measured in the machine room of the accident unit (the toxicity threshold is at of 345 ppm for a 1 hour exposure). Characteristic NH3 odours were perceptible off site. the NH3 concentrations were zero at the level of the accident unit which was put in cold stop. Half hour later toxicity was back to zero.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE could have been one of two options: (1) A rupture of a pipe near a valve carrying synthesis gas at 200 bar near a compressor of the unit, causing a high pressure burst perceived as an explosion, or (2) A gas release following by an unconfined vapour cloud explosion. After loss of confinement, the ignited hydrogen spread around the pipe affected pipe. The ROOT CAUSE is unknown.