Explosion on a hydrogen production unit
The incident involved an hydrogen-on-demand unit (HOD), which was installed inside an environmental test chamber used for reliability tests. An employee was troubleshooting the chamber, assessing the HOD unit. The chamber had been reported inoperative. Two units were being tested on a work bench, both were connected by an exhaust hose to the HOD. The gas had not been properly exhausted and began to back up into the hose that was attached to the HOD. The employee removed the side panel on the chamber and it exploded while he were standing in front of it. He was killed by the explosion.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the unexpected and undetected presence of hydrogen in the testing chamber when it was open to air. The conclusion of the OHSA legal investigation was that " the exhaust system was not designed, constructed, installed, tested and maintained properly to provide safety to life from fires and explosions. ". Therefore, the ROOT CAUSE was an inadequate design of the installation and of the related risk assessment, lack of operative and maintenance procedures, lack of proper safety measures.