Explosions and fire on the catalytic reforming unit of a refinery
A series of explosions occurred in thee desulphurisation and catalytic reforming unit of the refinery, followed by fires in the same unit. The establishment is classified as Seveso Upper Tier Class. The emergency, consisting in a series of domino effects, lasted almost one day. DETAILS of the INCIDENTS The fire, associated with muffled explosions, started at the desulphurisation unit section of the "cracker No. 7". It was caused by the rupture of a connection at the suction pipe of a pump, followed by ignition of the released cloud (about 200 kg of the substance) and the creation of a torch fire. The torch fire caused the rupture of an exposed 3-inch mineral oil pipe creating another fire jet of larger size. By further domino effects, collector, pipes and valves broke contributing to release of combustible substances. The ignited releases kept on burning until the material being processed in the unit was exhausted and the flare system could be isolated without risk.

The INITIAL CAUSE was the rupture of a connection on the suction part of a pump. Following the ignition of the 200 kg of products, and the failure to isolate the leak by not activation of the shut-off valve. Therefore a series of CONTRIBUTION CAUSES triggered a domino effect consisting in the fire-damage of other components with consequent release of additional flammable substances (liquid and gases). The ROOT CAUSE was related to a safety design which had not been able to take in account the possibility of domino effects.