Explosion on a hydro-treatment unit
The incident occurred at the hydrofining unit, refining a mixture of petroleum and diesel into Euro 3 and Euro 4 diesel. A pump feeding the reactor with the process mixture failed. Following the shutdown of this pump, a series of other events occurred which led to an explosion followed by fires. Detailed series of events: (1) After the pump stopped, the flow in the system dropped and the sense valve cracked. (2) The failure of the sense valve led to a reverse flow, filling the supply of the tank with a mixture of diesel and hydrogen at high pressure. (3) A series of communication alarms followed and at the same time the explosion occurred. (4) The explosion caused three fire flames in three directions: one at the exploding tank, one at a cracked pipe in the gas fractionation area and one on the ground in the tank area. There was one fatality and 5 injuries.

The INTIATING CAUSE was the failure of a pump. The ROOT CAUSE was shortcoming of the safety design: a series of single failures bought to an escalation of the initial incident, due to the absence of redundancy of the critical component. Moreover, the tank which failed due to over-pressure should have been equipped with a correctly dimensioned pressure relief device.