Explosion on a hydrogen compressor a space centre
A hydrogen-air explosion occurred outside a hydrogen compressor. Gaseous hydrogen was released from the vent stack due to a premature activation of a relief valve. The flammable atmosphere ignited and exploded, followed by a fire causing considerable damage. Following explosion, the shut-off valves were closed and system vented. The compressor unit included two relief valves downstream of a pressure regulator which had the role to reduce pressure from 5000 to 3000 psig (from 345 to 207 barg). The relief valve were downstream of regulator, in the 3000 psig system. The valves were sized to handle substantially different flows and one was designed for another program. The relief valve seemed to have opened prematurely when the system pressure was increasing from 2700 to 2900 psig (from 186 to 200 bar). The lack of accuracy of the 5000 psig gauge used to control the regulator control, combined with the tolerance of the relief valve settings (±3 percent) was sufficient to open the relief valve. Large flows were vented due to the large relief valve. In addition, the vent stack cap was designed so that the vented gases were released in a horizontal rather than vertical direction.

The INITATING CAUSE was the premature activation of a relief valve. The ROOT CAUSES were a combination of the use of inappropriate safety equipment and bad safe design (venting pipe horizontally places, no isolation valve between storage and compressor). It seems that part of the equipment was in place for another project, what indicate also bad (project) management.