HIAD Facility - Operational Condition: COMMISSIONING


The explosion occurred while starting up for the first time a hydrogenation reactor. The reactor was being commissioned, by performing tightness tests under hydrogen atmosphere at very high pressure.…
The explosion occurred at a ramjet engine of an aerospace testing centre. In order to carry out an airtight test on the engine, a pressure gauge was connected, the bolts on the hydrogen supply pipe…

This event occurred at the accelerator bubble chamber facility. During final stages of chmaber cooldown and its loading with LH2 (95% fill, about 95 gallons), an explosion and fire occurred…

During initial resting at a liquid hydrogen bubble chamber facility, an explosion occurred shortly after opening a high pressure hydroger line. The explosion was assumed to have taken place in the…

An explosion occurred at a aerospace testing centre, while testing a liquid hydrogen turbo-pump, part of a rocket engine. On the day of the incident, seven seconds after the rotation speed of the…
Hydrogen release and explosion due to a leak in a high pressure hydrogen storage tank, during first start-up of plant.
During functional tests of the system, a major quantity of hydrogen-containing gas was released from an adsorber, followed by its ignition. After the alarm was released the feed of the adsorber was…
The accident happened during testing of a hydrogen tank at a company which manufactured valves and other hydrogen-storage components. A dull bang and a huge pressure wave was felt kilometres away.…
The explosion and fire happened in a diesel hydro-treatment unit used to desulphurise raw diesel be means of hydrogen. The facility was expected to begin full commercial operations later in 2020.
The incident occurred in a workshop of a bus company. Hydrogen leaked from a tank on a new hydrogen and fuel cell bus parked there. The cause of the leak is unknown. From conversations with the…
A hydrogen and batteries driven aircraft was forced to land after a flight incident. According to the aircraft company the aircraft was forced to an emergency landing, but landed normally on its…
An explosion and fire occurred at a reciprocating recycle hydrogen compressor during commissioning of a new Diesel hydrotreatement Unit. It happened during the reactor pre-sulphidisation step, when…
The hydrogen buffer tanks that exploded were part of an experimental facility experimenting generation of renewable hydrogen from a water electrolyser coupled to solar panels. The three hydrogen…
During a leak test performed on a new retention basin of a chemical plant, one of the walls of the structure collapsed on a rack of 4 pipes located nearby and caused the rupture of the supports and…
The incident involves a gas booster provided by a manufacturer. This device is used in the experimental platform of the project to raise the pressure in pipelines from 60 to 80 barg (from 6 to 8 MPa)…

[Note of HIAD event validator: the description of this incident presents aspects which hinder the full understanding of the event sequence: for example, the PHMSA report uses the term ‘purge’ to…

The accidental hydrogen release occurred when testing the storage system connected to a PEM electrolyser. The leak test consisted in filling the storage with hydrogen at step-wise increase of…

The incident occurred in the new Residue Upgradation Facility unit of the refinery, which converts the heaviest oils from crude oil into high-quality, cleaner fuels such as Euro 6 diesel. The unit…

A university lab was investigating the production of hydrogen and methane from biomass made of wooden chips or sawdust. The experimental furnace was a concrete cylindrical furnace of the diameter of…

The incident occurred at the ammonia synthesis unit of a production plant of fertilizers (Seveso III upper tier), during the operation of start-up. The unit was restarting, when a pipe carrying…