Explosion and fire at a bubble chamber
During initial resting at a liquid hydrogen bubble chamber facility, an explosion occurred shortly after opening a high pressure hydroger line. The explosion was assumed to have taken place in the liquefier. Piping, transfer lines and dewar were ruptured. Hydrogen escaped and burned in a large cloud. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The liquid hydrogen was considered to contain about 2% contaminants, mostly oxygen. The single deoxidation unit was too small. The ignition source was attributed to an electric charge accumulated on solid oxygen as an insulator. The flow of high velocity gas produced the electric charge. With the layer of solid oxygen as insulator having an electric charge, a voltage across the insulator would be sufficient to break it down and cause a spark. The spark was most likely the ignition source.