An explosion on a hydrogenation reactor of a pharmaceutical products plant
The explosion occurred while starting up for the first time a hydrogenation reactor. The reactor was being commissioned, by performing tightness tests under hydrogen atmosphere at very high pressure. The rupture of one of the seals caused a hydrogen release followed by the auto ignition of a 30 litre air/hydrogen mixture. Five employees were injured. Material damage was confined to the immediate perimeter of the reactor. The hydrogen detectors controlling the closing of the H2 supply valve had not yet been installed. Nevertheless, their absence was not critical thanks to the prompt reaction taken by employees. The preliminary tests carried out under nitrogen were insufficient.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was the failing of a seal under hydrogen pressure during a tightness test. The root cause was the ill-designed or ill-performed commissioning procedure. The previous tightness under nitrogen were performed or designed in a way that did not identify the release event which occurred under hydrogen. The cause classification could be ‘operation’ or ‘design’.