Explosion in gases production plant
During functional tests of the system, a major quantity of hydrogen-containing gas was released from an adsorber, followed by its ignition. After the alarm was released the feed of the adsorber was closed, while the sprinkling system was activated by the high temperatures arising from the fire. The cause of this event was an assembly error, which caused the failure of a gasket (comb-shaped) at the head flange of the adsorber.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was an assembly error, which Caused the failure of a gasket It was due to human error during repair works. Root or contributing CAUSE could be an inadequate maintenance/installation procedure