A deflagration occurred during shutdown of a reactor used for ammonia synthesis. It was followed by a jet fire. The hydrogen leak was probably due first to the lower seals, followed by another leak…
The incident occurred in a hydrocracker unit of the refinery. A control valve on the liquid line between the high- and the low-pressure separators was erroneously opened and the liquid allowed to…
The event occurred at the hydrogen production unit of the ammonia production plant. An air-hydrogen mixture formed in the building hosting a water pump which fed water to a vessel that contained…
During functional tests of the system, a major quantity of hydrogen-containing gas was released from an adsorber, followed by its ignition. After the alarm was released the feed of the adsorber was…
A major leak (estimated between 1. 5 and 3 kg) of hydrogen from high-pressure storage, resulted in a detonation, from hydrogen a refuelling station. Causes were two untightened bolts securing the…
The event started when a gasket in a water pump was blown out. The water pump was situated inside a 100 m long, 10 m wide, and 7 m high building. The pump was feeding water to a vessel containing…
The release and fire occurred during what appeared to be a normal operation in a reactor section of a Residue Hydrotreater Unit, when an eight-inch pipe connected to a heat exchanger failed at the…
Several explosions occurred in one of the catalytic reforming units of the refinery, followed by a fire in the same unit. The fire derived from the explosions lasted for almost one day. The…
An operator had just replaced the ignition port cover on a hydrochloric acid plant burner. Normal start-up was continued by closing the drain valve in the product run off line and opening the…
Weld failure caused a fire involving a hydrogen pipe at a fertiliser ammonia plant. Source of ignition was auto ignition.
A leak occurred at an underground steel pipeline (6 inch) transporting pressurised hydrogen (75 bar). The leakage lasted for at least several hours, but it cannot be excluded that the leakage started…
A hydrogen fuel tank release caused a fire at a hydrogen refuelling station. A pressure relief valve installed on one of the 18 storage tanks failed at a pressure far below its design opening value.…
Fire in a ammonia plant. The accident starts with a leak of a hydrogen-nitrogen mixture at the suctionflange of a compressor. The mixture ignites on contact with air and the fire spreads to an oil…
Hydrogen and butyl acetate released and caught fire on the vent of a hydrogenation reactor, part of a dyes manufacturing plant. The pressure inside the reactor increased due to excess hydrogen…
The fire occurred in a unit to produce hexamethylenediamine, an organic compound precursor of polymers (HMD). The process is based on the hydrogenation of a precursor in presence of a catalyst. A jet…
A leak occurred on a 4 inch hydrogen main gas line which ran along a pipe bridge at the east end of a first stage compression plant building. The relased hydrogen ignited. The source of ignition was…
The accident originated in the isomerisation unit and propagated to the benzene saturation unit. The accident source was a mechanical rupture of one of the two compressors used to transfer hydrogen…
A 24" pipe carrying synthesis gas (Hydrogen = 43. 5%, Nitrogen = 14. 08%, Methane = 0. 2%, Carbon Dioxide = 12. 3%, Water = 29. 3% by volume) ruptured. About 60 kg of hydrogen contained in the gas…
The fire, 1 m high fire occurred in a pipe at the inlet of the hydrodesulphurisation unit of a refinery. The fire was caused by the leak of the pipe content, hydrogen and diesel fuel. According to…
The accident took place in a tank-type pressurised separator on the synthesis gas line of an ammonia production plant. The pressurised separator operates at nominal values of 25 bar and 5°C. It…