Explosion in an ammonia production plant
The event occurred at the hydrogen production unit of the ammonia production plant. An air-hydrogen mixture formed in the building hosting a water pump which fed water to a vessel that contained hydrogen gas at 30 bars. The triggering event was the blowing out of a gasket in the water pump. The pressure caused a back flow of water through the pump and out of the failed gasket. The hydrogen followed the same path, reaching the leakage point after approximately 3 minutes. The discharge of gas lasted 20 - 30 seconds before the explosion. The total discharge of hydrogen inside the building was about 10 - 20 kg. Most likely a hot bearing ignited the gas cloud. The main explosion was very violent, and it is likely that the gas cloud detonated. 3. 5 - 7 kg of hydrogen must have been burning during the explosion (no quantitative evidence that the cloud detonated, but from the damage observed, experience from other accidents and detonation experiments seemed most likely). The roof of the building was lifted by an estimated 1. 5 meters before resettling. The displacement of the roof caused a guillotine break of a 350 mm diameter pipe connected to the vessel that was the source of the original gas discharge. The gas composition in the vessel was 65 - 95 % hydrogen. This resulted in a large horizontal jet fire lasting about 30 seconds, outside the pumps building. Minor explosions occurred in the plant culvert system.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the loss of confinement of the water system, which allowed also the release of hydrogen, due to the failure of a gasket on the water pump. A wrong procedure caused the overheating of the pump and the failure of a gasket. The accident occurred when operators were trying to switch from one water pump to another. They did not realise that the inlet valve on the low-pressure side of first pump was closed. This resulted in a series of failed attempt to bring the situation back to normal. The root CAUSE was a combination of operational error, technical failures and weakness in the design. Moreover, the lack of diagnostics and automation did not helped personnel to understand the situation.