A hydrogen compressor had a major malfunction resulting in serious cavitations, vibrations and dead heading of the 1st stage. The incident resulted in 5 of the 8 lower head bolts on the first stage…
During a filling at a hydrogen refuelling station, the station was shut down due to a gas detection. The leak was extremely small and difficult to locate but the gas was directed upwards towards the…
The event occurred at the hydrogen production unit of the ammonia production plant. An air-hydrogen mixture formed in the building hosting a water pump which fed water to a vessel that contained…
A major leak (estimated between 1. 5 and 3 kg) of hydrogen from high-pressure storage, resulted in a detonation, from hydrogen a refuelling station. Causes were two untightened bolts securing the…
The event started when a gasket in a water pump was blown out. The water pump was situated inside a 100 m long, 10 m wide, and 7 m high building. The pump was feeding water to a vessel containing…
A 50-litre standard hydrogen gas cylinder was temporarily placed and used in a laboratory. The hydrogen gas was used for a flame ionization detector (FID) in gas chromatography (GC) instrument. The…
An oil leak in a hydrogen compressor was identified in the end of Aug 2015 by a technician performing regular maintenance on the compressor. The oil leak had caused a contamination of the entire…
The accidental hydrogen release occurred when testing the storage system connected to a PEM electrolyser. The leak test consisted in filling the storage with hydrogen at step-wise increase of…