Detection of hydrogen release
During a filling at a hydrogen refuelling station, the station was shut down due to a gas detection. The leak was extremely small and difficult to locate but the gas was directed upwards towards the gas sensor which shut down the station. The safety equipment performed well as it should and safely shutdown the station. The tiny leak was located about 8 cm from the end fitting in the middle of the hose. Discovered during inspection.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
It is suspected that the hose failure was due to an extreme temperature swing. It was the first really cold weather we had experienced being between -15 and -18c. The hose was sent back to the manufacturer for testing and no leak was found which was very interesting. The cause was never officially determined but the problem was resolved.