Detection of hydrogen release (401)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Detection of hydrogen release

During a filling at a hydrogen refuelling station, the station was shut down due to a gas detection. The leak was extremely small and difficult to locate but the gas was directed upwards towards the gas sensor which shut down the station. The safety equipment performed well as it should and safely shutdown the station. The tiny leak was located about 8 cm from the end fitting in the middle of the hose. Discovered during inspection.
Event Date
December 3, 2012
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
It is suspected that the hose failure was due to an extreme temperature swing. It was the first really cold weather we had experienced being between -15 and -18c. The hose was sent back to the manufacturer for testing and no leak was found which was very interesting. The cause was never officially determined but the problem was resolved.
Facility Information
Application Type
Application
Hydrogen dispenser
Specific Application Supply Chain Stage
Components Involved
High pressure dispenser hose
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Lessons Learned
All safety equipment operated as designed and shut the system down. In fact, if it were not for the hydrogen released, this could be classified as near-miss. Hoses are consumable parts; they damage quickly because they experience frequent pressure cycles characterised by very high pressures differences and temperature gradients. Moreover, they are also subjected to external mechanical stress such as bending and twisting during the filling.
Event Nature
Emergency Action
All safety equipment operated as designed and shut the system down.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Report provided but confidential