Skip to main content

Fire - at the vent stack of a hydrochloric acid production plant (508)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire - at the vent stack of a hydrochloric acid production plant

An operator had just replaced the ignition port cover on a hydrochloric acid plant burner. Normal start-up was continued by closing the drain valve in the product run off line and opening the combustion chamber condensate line. At this point a passing mechanic noted that a three foot hydrogen flame was burning from the vent stack. The plant was shut down. No evidence of an explosion or internal burning was identified. No source of ignition was identified for the flame. A small amount of charring occurred on the UPVC stack.
Event Date
October 3, 1977
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
no cause of the event was reported. Probably H2 accumulated in the condensate line which was then burned at the vent stack
Facility Information
Application Type
Application
Hydrochloric acid plant
Specific Application Supply Chain Stage
Components Involved
Reactor vent stack
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
An operator had just replaced the ignition port cover on a hydrochloric acid plant burner. Normal start-up was continued by closing the drain valve in the product run off line and opening the combustion chamber condensate line.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (offsite)

0

Event Nature
Emergency Action
A passing mechanic noted that a three foot hydrogen flame was burning from the vent stack. The plant was shut down. No evidence of an explosion or internal burning was identified. No source of ignition was identified for the flame. A small amount of charring occurred on the UPVC stack.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Event description extracted from the UK database ICHEME in PDF ICHEME database is no longer available for purchase, but data can be download as PDF for free. https://www. icheme. org/knowledge/safety-centre/resources/accident-data/ (accessed October 2020)