Fire from a hydrogen storage tank
A hydrogen fuel tank release caused a fire at a hydrogen refuelling station. A pressure relief valve installed on one of the 18 storage tanks failed at a pressure far below its design opening value. The failure triggered the immediate release of approximately 30 kg of hydrogen in the first minute and a total of approximately 300 kg. This rapid release of hydrogen mixed with air in the vent tube and subsequently ignited producing the loud “boom” reported by eye and ear witnesses. After the pre-mixed gases were consumed the venting hydrogen produced a jet flame emanating from the outlet of the vent system. The flames from this vent scorched the top of the canopy of the manual dispenser causing combustion of the paint and dust and superficial damage to the canopy. The fire lasted for more than 2 hours, at which point the local fire department allowed technicians of the stations and experts to enter the station and stop the flow of the gas. The fire brigades and the local authorities evacuated several businesses and a high school and closed several road intersections.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the accidental activation of a pressure relief valve installed on one of the storage tanks. The pre-mature failure was the use of materials that were incompatible with hydrogen services (440C steel is affected by embrittlement in presence of hydrogen). ROOT CAUSE was a design shortcoming. A CONTRIBUTING CAUSE to the escalation of the event was the lack of timely information regarding the status of the system. Another CONTRIBUTING CAUSE was the station design (interaction of canopy and venting system).