Fire in a chemical plant (189)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a chemical plant

Hydrogen and butyl acetate released and caught fire on the vent of a hydrogenation reactor, part of a dyes manufacturing plant. The pressure inside the reactor increased due to excess hydrogen resulting from a faulty pressure measurement, till a safety valve opened and released the gas: the event took place on the roof, the roof vent was equipped with a flame arrestor. The wrong pressure reading was caused by the clogging of the connection used for the pressure measure. The rector’s hydrogen supply and the injection of nitrogen in the installation were stopped. The Classified Installations Inspectorate performed an investigation.
Event Date
April 12, 2002
Record Quality Indicator
Region / Country
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was due to the fact that the pressure gauge inside the reactor was not working well due to clogging of a connector. The investigation revealed the following ROOT or CONTRIBUTING CAUSES: 1. A lack of an explosive zone in the area around the vent, despite the presence of electrical equipment in the immediate vicinity (lighting, ventilation, air conditioners). 2. Some of this equipment was explosion-proof, but it was not clear is designed for the class of gases to which hydrogen belongs. 3. The opening of the valve and the release of gases and flammable vapours were detected belatedly.
Facility Information
Application Type
Application
Dyes and pigments productions
Specific Application Supply Chain Stage
Components Involved
hydrogenation reactor
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The pressure in the reactor was higher than normal, due to a wrong pressure reading.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (offsite)

0

Post-event Summary

All the equipment located in the surrounding of vents, susceptible to free flammable gas, will be checked for ATEX conformity. ATEX zoning will be made around each vent. Safety systems and monitoring will be doubled and regularly checked.

Investigation Comments

The report found: 1. The lack of an explosive zone in the area around the vent despite the presence of electrical equipment in the immediate vicinity (lighting, ventilation, air conditioners). 2. Some of this equipment was explosion-proof, but it was not clear is designed for the class of gases to which hydrogen belongs. 3. The opening of the valve and the release of gases and flammable vapours were detected belatedly.

Event Nature
Emergency Action
Feeding of hydrogen and nitrogen was stopped.
Emergency Evaluation
The safety valve worked as designed, releasing the hydrogen to the roof without any further consequence.
Release Type
Release Substance
H2, butyl acetate
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Incident firstly reported by ARIA