Fire in a chemical plant
Hydrogen and butyl acetate released and caught fire on the vent of a hydrogenation reactor, part of a dyes manufacturing plant. The pressure inside the reactor increased due to excess hydrogen resulting from a faulty pressure measurement, till a safety valve opened and released the gas: the event took place on the roof, the roof vent was equipped with a flame arrestor. The wrong pressure reading was caused by the clogging of the connection used for the pressure measure. The rector’s hydrogen supply and the injection of nitrogen in the installation were stopped. The Classified Installations Inspectorate performed an investigation.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was due to the fact that the pressure gauge inside the reactor was not working well due to clogging of a connector. The investigation revealed the following ROOT or CONTRIBUTING CAUSES: 1. A lack of an explosive zone in the area around the vent, despite the presence of electrical equipment in the immediate vicinity (lighting, ventilation, air conditioners). 2. Some of this equipment was explosion-proof, but it was not clear is designed for the class of gases to which hydrogen belongs. 3. The opening of the valve and the release of gases and flammable vapours were detected belatedly.