Fire in an ammonia production plant (796)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Fire in an ammonia production plant
The accident took place in a tank-type pressurised separator on the synthesis gas line of an ammonia production plant. The pressurised separator operates at nominal values of 25 bar and 5°C. It contains a mixture of hydrogen and nitrogen (75%/25%). It is located slightly upstream of the synthesis gas compressor (on the low pressure side) that was shut down. The connector connecting the separator to its level measuring instrument is located outside, near the building containing the compressors. The connector is thermally insulated (gas inside at 5°C) over its entire length. The leak took place at the point of connection between the separator and its level measuring instrument. 1. First a compressor on the synthesis gas circuit was shut down following a malfunction. 2. When the compressor stopped, there was a slight increase in pressure (25 -> 29 bar) upstream (at the low pressure end). Normal pressure is roughly 25 bar, and the system is protected by a 30 bar pressure relief valve. 3. The pressure of 29 bar, although not too high for the installation, caused the connecting pipe to break because of heavy wear resulting from undetected corrosion under the insulation. 4. A leak of hydrogen (25 bar) occurred and caught fire. A flame jet approximately 10 metres high then damaged various surrounding installations (domino effect). Equipment containing oil that became engulfed by the flame jet also caught fire. The flame jet was extinguished by closing a valve located upstream of the hydrogen leak. Once the valve had been closed, the flame jet gradually became smaller and smaller until the hydrogen from the installations between the valve and the leak had burnt off completely. The company’s emergency response team fought the (oil) fire and cooled the equipment near the flame jet so as to minimise damage. Although no one was hurt in the accident, the damage caused (solely on the company’s premises) was significant, and the plant had to be shut down for several months for repairs. Approximately 700 kg of hydrogen was estimated released.
INITIATING cause was failure of a pipe below the nominal operative values due to undetected corrosion. ROOT CAUSE was a lack of an effective procedure for preventive inspection of damage.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.