Fire in a hydrogen pipe (546)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a hydrogen pipe

A leak occurred on a 4 inch hydrogen main gas line which ran along a pipe bridge at the east end of a first stage compression plant building. The relased hydrogen ignited. The source of ignition was hot welding sparks arising from work being carried out by contract personnel whilst installing a new chlorine line above the hydrogen main on the pipe-bridge. Before the welding work was carried out, an explosivity test had been carried out in the area and a 0 explosive gas result had been reproted in the work permit. An investigation into the incident found that the removed section of the hydrogen main revealed an elliptical hole 2 centimetres x 1 and a half centimetres. It was only when the lagging was disturbed that the hydrogen leak became obvious. The area around the hole in hydrogen main was very pitted suggesting that the failure was due to localised corrosion.
Event Date
October 2, 1979
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITATING CAUSE was an elliptical hole of 2 centimetres x 1. 5 centimetres. It was very probably due to localised corrosion. The leak was not detected during the explosivity test because of a build up of scale sealing the hole, possibly dislodged later by the activities of the contractors in the area. THe technival reason for the corrosion is not povided or known. Neverhtless, ROOT CAUSE could be possibly attributed to a lack of effective inspection, not able to detect the progress of the corrosion.
Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
Separation equipment
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary

Welding works were ongoing, but the plant had not been shutdown (pesene of flammabe gases had been excluded by measures).

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Emergency Action
The welder saw the hole appeared as if the lagging on the pipe had caught fire and an unsuccessful attempt was made to put it out using carbon dioxide fire extinguishers and then water.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Hole Shape
Hole Length (mm)
2
Hole Width (mm)
1
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Event description of the UK database ICHEME in PDF. The ICHEME database is no longer available , but data can be download as PDF for free. https://www. icheme. org/knowledge/safety-centre/resources/accident-data/ (accessed October 2020)