Fire in a refinery (185)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a refinery

The accident originated in the isomerisation unit and propagated to the benzene saturation unit. The accident source was a mechanical rupture of one of the two compressors used to transfer hydrogen mixtures to the isomerisation unit. The rupture caused the release of a gas mixture containing hydrogen, which ignited by mixing with air, forming a jet fire. The jet fire was directed towards the adjacent benzene saturation unit, hitting a pressure vessel located 14 m from the release point (the jet flame could have been 30 m long in absence of obstacle). The weakening of this vessel caused the release benzene, which contributed to extend the fire. Due to the fact that the process control records did not register significant changes in the process parameters it has to be assumed that the failure of the crank mechanism was caused by aspects linked to maintenance or by a material defect. Off-site fire brigade teams intervened extinguishing the fire within approximately 1 hour and a half of work. No damage was reported to persons or to the environment.
Event Date
December 27, 2002
Record Quality Indicator
Region / Country
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE of the fire was the mechanical failure of a hydrogen compressor. The root CAUSE was the failure in considering the possibility of domino effects from the fire in the isomerisation unit (whose risk had been considered in the risk assessment).
Facility Information
Application Type
Application
Hydroisomerisation process
Specific Application Supply Chain Stage
Components Involved
Isomerisation unit, gas compressor
Storage/Process Medium
Actual Pressure
20
Design Pressure
20
Location Type
Location description
DESCRIPTION OF THE PROCESS The aim of a isomerisation unit is to converts linear molecules (e. g. pentane) into higher-octane branched molecules for blending into the end-product gasoline. It is also used to convert linear normal butane into isobutane for use in the alkylation unit. it requires the feed of hydrogen. The release occurred on one of the two compressors working in parallel at a pressure of 20 bars, conveying the gas mixture needed for the isomerisation process. PLANT QUANTITIES Maximum amounts of substances registered in the plant inventory were: - approximately 25,000 m3 of hydrogen rich gas mixture, therefore 1,500 m3 of pure hydrogen (approximately 1,5 tons). - 147000 t of liquid automotive petrol. The establishment extends over a surface of 100 ha.
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

2000000

Property Loss (offsite)

500000

Post-event Summary

No damage was reported to persons or to the environment. The damage to the equipment has been evaluated around 2 to 3 MEuro, depending on the source. The benzene saturation unit was destructed; only a small part of the equipment could be recovered. In the isomerisation unit the loss of the compressor was registered, the compressor had practically to be completely substituted and was taken back into service in six months later. Total estimated released quantities : 3 t gas mixture from the isomerisation unit + 0. 3 t gas mixture of the benzene saturation unit, for a total of approximately 3. 3 tons of gas mixture with 70% volume of H2, corresponding to approximately 10% in weight. 6 t gasoline from the isomerisation unit + 6 t gasoline present in the benzene saturation unit for a total of 12 tons of gasoline.

Event Nature
Emergency Action
15:00 - A loud abnormal noise coming from the isomerisation unit was heard by the personnel working near that unit. Having identified the in the compressor the cause of the noise, they tried to stop it via the emergency shut-off switch. In the control room the emergency shut-down procedure was activated, triggering the a rapid depressurisation by blowing down the system. Immediately afterwards a violent release of a hydrogen rich gas mixture occurred from the compressor bottom, the jet ignited almost instantly and hit the adjoining part of the benzene saturation unit. The refinery personnel closed the manual valves installed on the pipe mains and started to extinguish the fire, activating the fixed cooling systems and the foaming system of the units involved and nearby units. 15:03 - the onsite Emergency Control Centre team gathered and established communication with the Advanced Control Centre. 15:12 - Off-site fire brigade alerted. Meanwhile the on-site emergency response team fought the fire with a fixed and mobile extinguishing units from all sides. 15:16 - Emergency shut-down procedure started for the entire establishment. 15:30 - First off-site fire brigade team on-site, supporting response operations. 15:50 The size of the fire greatly reduced by because the compression section of the plant no longer fed the fire; fire continued in the benzene unit engulfing it with flames. 16:25 the fire almost extinguished; cooling operations continued. 16:50 the emergency called off.
Emergency Evaluation

The accident could have caused more severe damage without the adoption of effective response measures and the joint effort of the on-site personnel and the off-site fire brigades; even if the on-site emergency response organisation could be improved.

Release Type
Release Substance
H2 70% gasoline, hydrocarbons
Hydrogen Release Concentration (%)
0.00
Release Amount (kg)
3000.00
Release Pressure (bar)
20.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Event from the European database eMars https://emars. jrc. ec. europa. eu/en/emars/accident/view/8bb6d0cc-dd21-2926-53b3-9c7d158097be

Full investigation report from French database ARIA (event 26983) https://www. aria. developpement-durable. gouv. fr/fiche_detaillee/26983_en/?lang=en