Fire in a refinery
The accident originated in the isomerisation unit and propagated to the benzene saturation unit. The accident source was a mechanical rupture of one of the two compressors used to transfer hydrogen mixtures to the isomerisation unit. The rupture caused the release of a gas mixture containing hydrogen, which ignited by mixing with air, forming a jet fire. The jet fire was directed towards the adjacent benzene saturation unit, hitting a pressure vessel located 14 m from the release point (the jet flame could have been 30 m long in absence of obstacle). The weakening of this vessel caused the release benzene, which contributed to extend the fire. Due to the fact that the process control records did not register significant changes in the process parameters it has to be assumed that the failure of the crank mechanism was caused by aspects linked to maintenance or by a material defect. Off-site fire brigade teams intervened extinguishing the fire within approximately 1 hour and a half of work. No damage was reported to persons or to the environment.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE of the fire was the mechanical failure of a hydrogen compressor. The root CAUSE was the failure in considering the possibility of domino effects from the fire in the isomerisation unit (whose risk had been considered in the risk assessment).