Skip to main content

Explosions and fire in a refinery (227)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosions and fire in a refinery

Several explosions occurred in one of the catalytic reforming units of the refinery, followed by a fire in the same unit. The fire derived from the explosions lasted for almost one day. The complexity of the event was determined by the various domino effects which took place. The accident chronology was as follows:A) rupture of a 3/4 inch tapping (connection) on the suction pipe of pump;B) after 30 s, ignition of the cloud (about 200 kg of the substance) and creation of a (combustible) fed torch fire;C) after additional 30 s, rupture of a 3-inch mineral oil pipe which was exposed to the torch fire, creating another fire jet of larger size;C) after 5 minutes, by domino effect, rupture of the collector of a cooling tower and ignition of the released substances used in the process;C) after 5 minutes, by domino effect, rupture of the 8-inch head pipe of a reformer column, ignition of the release, rupture of column valves collector, which is connected to the site's flare system, and ignition of the released gas. This caused a partial release to the atmosphere from the site's flare system. The ignited releases kept on burning until the material being processed in the unit was exhausted and the flare system could be isolated without risk. The accident caused minor injuries to one person. There was no significant environmental impact. Fire extinguishing water was stored in a 60. 000 m3 buffer tank designed this purpose. The accident caused a 7-month shutdown of the unit. The causes of the accident are related to a system constituted of "steam turbine + pump" (Ref. P3B). Actually, the accident occurred during a periodical test phase carried out with this equipment, which constitutes an emergency relief unit for the P3A pump. Various investigations carried out after the accident, have led to the identification of a complex of factors which may have caused the accident itself.
Event Date
September 3, 2000
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was related to a system constituted of a "steam turbine + pump". The accident occurred during a periodical test phase carried out with this equipment, which constitutes an emergency relief unit for another pump. Various investigations carried out after the accident, have led to the identification of a complex of factors which may have caused the accident itself, such as Presence of condensates in the turbine, Inadequate design of the pump (foundation, lubrication rotor, cavitation, etc. )These factors caused strong vibrations followed by fatigue stress to and the rupture of the connection placed just above the pump. The vibration caused as well a misalignment of the turbine and the pump, which caused a fracture of the shaft and a deterioration of the coupling. A contributing cause which worsened the consequence of he INITIATING cause was an anomalous delay of about 10 min in closing the block valve of the feeding pipe of the pump. If the closing of this valve had been completed within the normal time of about one minute, the domino effects involving the other pipe networks could have been avoided.
Facility Information
Application Type
Application
catalytic reforming process
Specific Application Supply Chain Stage
Components Involved
catalytic reforming reactor, cracker, steam turbine, pump
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE PLANT The plant is a very large refinery with a crude oil distillation capacity of 17 millions tons/year. The plant is classified as Seveso Upper Class. The unit involved in the accident is a catalytic reforming unit used to produce high-octane gasoline fractions. This unit can process 4200 t/day of product. The unit consists of 3 successive sections: a de-sulphurisation section, a catalytic reforming section, and a fractionation section. The substances used in the process are mainly flammable substances (mineral oils, hydrogen), and gases like hydrogen and H2S hydrogen sulphide.
Operational Condition
Pre-event Summary
The accident occurred during a periodical test phase of the unit which failed first.
Consequences
Number of Injured Persons
2
Number of Fatalities
0
Currency
Property Loss (onsite)
72000000
Property Loss (offsite)

0

Post-event Summary

The accident caused minor injuries to two fire fighters. There was no significant environmental impact, and the extinguishing water has been stored in a 60. 000 m3 buffer tank designed this purpose. The accident has caused a 7-month shutdown of the unit. The material damage amounts to about 13. 72 MEuro for repairs and 68. 6 MEuro for production loss.

Investigation Comments

Various investigations carried out after the accident, have led to the identification of the complex factors which may have caused the accident itself.

Event Nature
Emergency Action
The emergency response operations in this accident were carried out by the on-site fire fighting service of the refinery, supported by the neighbouring city's fire brigade. The fire fighting strategy was based on reducing the risk of fire propagation and cooling the structures which were exposed to thermal radiation, in order to prevent a possible collapse. At the climax of the fire, large water delivery rates were employed (of the order of 2300 m3/h, with a pressure of 7 to 8 bar, supplied by the extinguishing system of the installation).
Release Type
Release Substance
H2, H2S, hydrocarbons
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Event description in the European database eMARS https://emars. jrc. ec. europa. eu/en/eMARS/accident/view/2be5b50d-386f-8a89-4f37-5910aca86f41 (accessed September 2020)

Detailed event report in the French database ARIA https://www. aria. developpement-durable. gouv. fr/wp-content/files_mf/A19423_ips19423_001. pdf (accessed September 2020)