Explosions and fire in a refinery
Several explosions occurred in one of the catalytic reforming units of the refinery, followed by a fire in the same unit. The fire derived from the explosions lasted for almost one day. The complexity of the event was determined by the various domino effects which took place. The accident chronology was as follows:A) rupture of a 3/4 inch tapping (connection) on the suction pipe of pump;B) after 30 s, ignition of the cloud (about 200 kg of the substance) and creation of a (combustible) fed torch fire;C) after additional 30 s, rupture of a 3-inch mineral oil pipe which was exposed to the torch fire, creating another fire jet of larger size;C) after 5 minutes, by domino effect, rupture of the collector of a cooling tower and ignition of the released substances used in the process;C) after 5 minutes, by domino effect, rupture of the 8-inch head pipe of a reformer column, ignition of the release, rupture of column valves collector, which is connected to the site's flare system, and ignition of the released gas. This caused a partial release to the atmosphere from the site's flare system. The ignited releases kept on burning until the material being processed in the unit was exhausted and the flare system could be isolated without risk. The accident caused minor injuries to one person. There was no significant environmental impact. Fire extinguishing water was stored in a 60. 000 m3 buffer tank designed this purpose. The accident caused a 7-month shutdown of the unit. The causes of the accident are related to a system constituted of "steam turbine + pump" (Ref. P3B). Actually, the accident occurred during a periodical test phase carried out with this equipment, which constitutes an emergency relief unit for the P3A pump. Various investigations carried out after the accident, have led to the identification of a complex of factors which may have caused the accident itself.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was related to a system constituted of a "steam turbine + pump". The accident occurred during a periodical test phase carried out with this equipment, which constitutes an emergency relief unit for another pump. Various investigations carried out after the accident, have led to the identification of a complex of factors which may have caused the accident itself, such as Presence of condensates in the turbine, Inadequate design of the pump (foundation, lubrication rotor, cavitation, etc. )These factors caused strong vibrations followed by fatigue stress to and the rupture of the connection placed just above the pump. The vibration caused as well a misalignment of the turbine and the pump, which caused a fracture of the shaft and a deterioration of the coupling. A contributing cause which worsened the consequence of he INITIATING cause was an anomalous delay of about 10 min in closing the block valve of the feeding pipe of the pump. If the closing of this valve had been completed within the normal time of about one minute, the domino effects involving the other pipe networks could have been avoided.