Explosion of a tank at hydrogen components manufacturer (1083)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion of a tank at hydrogen components manufacturer

The accident happened during testing of a hydrogen tank at a company which manufactured valves and other hydrogen-storage components. A dull bang and a huge pressure wave was felt kilometres away. News report massive damage to the test facility, but a very small fire. Still according to the news, the most probable cause emerging from the investigation is the over-pressuring of the tank due to an erroneous connection. While the news speak of a connection to a compressed air hose, another source specifies that it has been a 900 bar gas connection to a tank designed for a nominal working pressure of 350 bar. This is the most plausible explanation.
Event Date
August 8, 2023
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the erroneous connection to a pressurised gas source much higher than the maximal pressure of the tank. The sources report the company statement that material or component malfunctions could be excluded and that the ROOT CAUSE was a human error. Due to the lack of details, it is not known if the event was the result of not following the procedures, or if there were shortcoming in the procedures, and therefore both causes are attributed to this event .
Facility Information
Application Type
Application
CH2 stationary tank
Specific Application Supply Chain Stage
Components Involved
tank
Storage/Process Medium
Storage/Process Quantity
0
Actual Pressure
90
Design Pressure
35
Location Type
Operational Condition
Pre-event Summary
The tank was being tested. Since this incident seems to be related to high pressure failure only, and not to fire and chemical explosion, it could be assumed that the gas used for testing was an inert gas.
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Post-event Summary

One worker was slightly injured, massive damage to the test facility, a very small fire.

Event Nature
Emergency Action
Fire brigade and police evacuated the surrounding areas and set up cordons within a radius of around 500 meters, because the explosion of another even larger hydrogen tank could not be ruled out. The nearby highway was closed in both directions and a specific area of the airspace was also blocked.
Release Type
Release Substance
air 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

ORF news of 13/09/2023 cotnaining a first expnation of causes https://steiermark. orf. at/stories/3223951/ (accessed Sep 2023)

ORF news of 09/08/2023 cotnaining a first expnation of causes https://steiermark. orf. at/stories/3219226/ (accessed Sep 2023)

Presentation by the US H2 Centre for Hydrogen Safety, given to the workshop "Gulf Coast Hydrogen Ecosystem: Opportunities and Solutions,” https://uh. edu/uh-energy-innovation/uh-energy/energy-symposium-series/2023-2024/hydrogen-ecosystem/_files/psr-session-1---barilo---cfhs---hydrogen-incidents-and-lessons-learned. pdf (accessed Dec 2024)