Hydrogen compressor explosion and fire at a refinery.
An explosion and fire occurred at a reciprocating recycle hydrogen compressor during commissioning of a new Diesel hydrotreatement Unit. It happened during the reactor pre-sulphidisation step, when the recycle gas contained 9000 ppm of H2S (hydrogen sulphide) and the pressure was at 940 psig (65 bar). The failure of retaining bolts on head-end suction valve unloader of recycle cylinder on compressor allowed release of process gas. Investigations revealed that the bolts failed due to material inappropriate to prevent sulphide stress cracking) and inadequate design for the service. The manufacturer did not comply with the company's practice for reciprocating compressors in H2S applications. The compressor was damaged.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the failure of valve bolts on the hydrogen compressor which recycles the H2S-containing hydrogen coming from the hydrotreater. Contributing causes were an inadequate design, the choice of incorrect material and stress corrosion cracking