Safety disc ruptured on LH2 tanker during offloading. The supply was refused due to possible contamination. [Ordin, NASA (1974)]
While disconnecting the liquid hydrogen filling line from the tanker, hydrogen escaped burning the man who was holding the hose; he was burned on hands and stomach. [Ordin, NASA (1974)]
During an LH2 transfer from a tanker, the burst disc ruptured at 50 psi (ca. 3. 5 bar). The operator had turned on the pressure valve and left it unattended, permitting pressure build-up past the…
While pressurizing a liquid hydrogen tanker for the transfer, a rupture disc burst. The tanker pressure was 22 psig (ca. 1. 5 bar). The relief valve was set at 27 to 29 psig (1. 9 to 2 bar). The…
During preparations for off-loading of a commercial tanker, the trailer experienced an overpressure causing the 50 psig (ca. 3. 5 bar) relief valve to open and also the rupture of the 70 psig (ca.…
A liquid hydrogen trailer was delivering hydrogen at a customer site. The operation was occurring at the correct pressure, when one burst disc failed prematurely. No ignition occurred. The…
During sampling tests on a facility LH2 dock transfer system, the system was pressurized to 15 psig when an expansion joint ruptured. Technicians proceeded with the pressure cycle with the main…
This event summarises 3 very similar cases of leaks at dispenser hoses during refuelling, occurred at the same hydrogen refuelling station in the period January - April 2017. The leaks triggered…
A leak occurred when transferring hydrogen from a trailer to the customer storage. The driver had just completed the pre-fill procedures and was starting to apply pressure to the fill hose, when…
"A leak occurred when transferring gaseous hydrogen from a tube trailer to the well of a hydrogen underground storage test facility. The leak was located at a threaded fitting which was part…
A leak developed on a CGH2 tube trailer on the pigtail of one of the tube. The pigtail was cracked, possibly due to vibration. This trailer was tested the day before this incident and was found to…
A liquid hydrogen tanker had completed the off-loading at a customer’ site (metal manufacturer). The drivers were preparing to disconnect from the customer’ tank, when they noticed a small leak at…
During loading of a LH2 storage tank, the vent valve on the tank was opened and then ignition occurred near the instant that the valve was fully open. A light pressure wave was produced. The cloud…
During transfer operations of a liquid hydrogen from a tanker, a release of hydrogen occurred, which resulted in the detection of hydrogen in an adjacent building. The normal procedure could not…
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.